工業設備技術領導者 (儲冰槽、冷卻水塔、發電機激磁系統)
Global Leader in Ice Thermal Storage
PT2
型錄 | 規範 | 實績 | 照片 | 圖面 |
材質 | 特點 | 技術 | CTI 認證 |
Construction Options
- Standard: – All steel panels and structural members are constructed of heavy-gauge G-235 (Z700 metric) hot-dip galvanized steel. The air inlet louvers are constructed of PVC and are individually removable without tools.
- Optional TriArmor® Corrosion Protection System – The cold water basin can be constructed with the TriArmor® Corrosion Protection System. The system consists of a heavy-gauge G-235 hot-dip galvanized steel substrate encapsulated in a special thermosetting hybrid polymer finish further protected by a polyurethane liner applied to all submerged surfaces of the cold water basin. The basin is leak tested at the factory and warranted against leaks and corrosion for 5 years.
- Optional EVERTOUGH™ Construction – The EVERTOUGHTM Construction option combines BAC’s exclusive thermosetting hybrid polymer and TriArmor® Corrosion Protection Systems to provide the best value in corrosion protection for most water chemistries. All heavy-gauge G-235 galvanized steel panels and structural members are protected with a thermosetting hybrid polymer. The cold water basin is constructed with the TriArmor® Corrosion Protection System. The basin is leak tested at the factory and warranted against leaks and corrosion for 5 years. Each cooling tower provided with EVERTOUGH™ Construction is backed by a comprehensive Louver-to-LouverSM five-year warranty, which covers ALL components from the fan to the cold water basin, from louver to louver, including the motor.
- Optional Thermosetting Hybrid Polymer – The thermosetting hybrid polymer coating used to extend equipment life is applied to selected hot-dip galvanized steel components of the cooling tower. This finish has been tested to withstand 6000 hours in a 5% salt spray without blistering, chipping, or loss of adhesion.
- Optional Stainless Steel Cold Water Basin – The cold water basin can be constructed of Type 304 stainless steel. All factory seams in the cold water basin are welded to ensure watertight construction and warranted against leaks for 5 years.
- Optional All Stainless Steel Construction – Panels and structural elements are constructed of Type 304 stainless steel. All factory seams in the cold water basin are welded to ensure watertight assembly and warranted against leaks. The basin is leak tested at the factory and all factory seams are warranted against leaks for 5 years.
- Rated in accordance with IBC regulations to meet Seismic and Wind Loadings – Standard construction and optional construction with structural bracing is designed to meet requirements of International Building Code covering most US seismic applications in addition to withstanding wind loads up to 130 psf.
- Low Sound Operation–The low sound levels generated by PT2 Cooling Towers make them suitable for installation in most environments. For sound sensitive installations, the PT2 is available with a low sound fan that significantly reduces the sound levels generated from the tower with minimal impact on thermal performance (low sound fans are not available on Model PT2-0412A). The cooling tower thermal performance with the low sound fan has been certified in accordance with CTI Standard STD-201. For sound sensitive installations, factory designed, tested and rated water silencers and discharge sound attenuation are also available for PT2 Cooling Towers.
Containerized For Export

Single Unit in 20' Container
- Over 400 Tons in a single 40′ Shipping Container
- Engineered for:
- The worldwide export market
- Maximum capacity
- Designed to fit a single unit in a 20′ container
- Designed to fit two units in a 40′ container
- Easy maintenance
- Reliability
- Lowest Shipping Costs!
Units are factory assembled and require only minimal assembly and rigging!